FAQ

Cable Cross-Section per Circuit Breaker: Which Cable for Which Protection?

Read AREI Book 1 V06 Table 4.11 correctly: its legal ceiling is not a complete cable calculation. See Table 5.1, old EMCB and EMCVB wiring, and voltage drop.

Published on 18 March 2026 Updated on 29 August 2026 8 min

Cable Cross-Section per Circuit Breaker

The protective device protects the wiring, not the connected appliance. A breaker that is too large for the wiring can allow the wiring to heat for too long during an overload. But choosing correctly involves more than looking up a size: the load, the cable and the installation conditions must be assessed together. This guide explains what AREI Book 1 V06 Table 4.11 does establish and what a complete design still has to check.

Reading Table 4.11 in the other direction

Table 4.11 in subsection 4.4.1.4 gives, for domestic installations, the maximum rated current of a fuse and a circuit breaker for each conductor cross-section. The inverse overview below is therefore a legal table ceiling for the cross-section, not a universal guarantee that a cable of that size is adequately designed in every situation.

Circuit breakerSmallest cross-section shown by Table 4.11Example use
10 A1.5 mm² for fixed domestic circuits; 1 mm² appears in the table but not in Table 5.1 for new fixed wiringLighting without socket outlets
16 A1.5 mm² under Table 4.11, but socket circuits require at least 2.5 mm² under 5.2.1.2Lighting or a circuit without sockets
20 A2.5 mm² as the table ceilingDedicated final circuit, if other checks allow it
25 A4 mm²Final circuit with a higher load
32 A6 mm²Dedicated higher-power load
40 A6 mm²Supply or heavy final circuit, after a complete calculation
63 A10 mm²Sub-distribution board supply, after a complete calculation
80 A16 mm²Supply wiring, after a complete calculation
100 A25 mm²Supply wiring, after a complete calculation

The 2.5 mm² detail matters: Table 4.11 gives 16 A as the maximum rated current for a fuse and 20 A for a circuit breaker. That does not automatically make a 20 A breaker correct on every 2.5 mm² cable. Installation method, load, voltage drop, short-circuit conditions and cable type still need checking. For a socket circuit, the minimum cross-section from 5.2.1.2 still applies even if a lower-rated protective device is selected.

The complete Table 4.11

Conductor cross-sectionMax. fuseMax. circuit breakerMeaning
0.5 mm²2 A4 AControl, monitoring, signalling and measurement circuits only
0.75 mm²4 A6 ACircuits built into distribution and switchgear assemblies
1 mm²6 A10 ANo new fixed-wiring exception in Table 5.1
1.5 mm²10 A16 ACircuits without socket outlets
2.5 mm²16 A20 AGeneral Table 4.11 category
4 mm²20 A25 AGeneral Table 4.11 category
6 mm²32 A40 AGeneral Table 4.11 category
10 mm²50 A63 AGeneral Table 4.11 category
16 mm²63 A80 AGeneral Table 4.11 category
25 mm²80 A100 AGeneral Table 4.11 category
35 mm²100 A125 AGeneral Table 4.11 category

The two protection columns are not interchangeable. Replacing a 16 A fuse with a 20 A breaker on 2.5 mm² increases the permitted rated current and therefore calls for a new assessment; the table only places both maximum values next to each other.

Why the table is not enough

A correct design starts with the design current Ib, meaning the current expected from the load. The rated current In of the protective device and the permissible current-carrying capacity Iz of the wiring are then selected. A common check is Ib ≤ In ≤ Iz, together with the required protective-device characteristics. Iz is not a fixed value determined by cross-section alone.

The assessment must include, among other things:

  • conductor material, insulation and cable construction;
  • installation method (in conduit, in thermal insulation, on a wall, in a bundle or on a cable tray);
  • the number of simultaneously loaded conductors and grouping factors;
  • ambient temperature, heat dissipation and external influences;
  • length, load and permissible voltage drop;
  • disconnection conditions during a short circuit and fault-loop impedance;
  • the protective device’s breaking capacity compared with the prospective short-circuit current.

The protection must therefore be compatible with the cross-section thermally and with the real circuit. A long cable run may need a larger cross-section to control voltage drop. An unfavourable installation method can reduce Iz. A breaker with an acceptable rated current can still be unsuitable if the fault loop does not permit the required automatic disconnection or if its breaking capacity is too low for the prospective fault current.

Table 5.1: limited exceptions below 2.5 mm²

Subsection 5.2.1.2 generally prohibits insulated conductors smaller than 2.5 mm² when they are not an integral part of a machine or appliance. Table 5.1 lists the exceptions:

MinimumOnly for
1.5 mm²Wiring in circuits without sockets, except an individual socket rated no more than 2.5 A that is built into a luminaire
0.75 mm²Circuits built into distribution and switchgear assemblies that supply one single socket outlet; the protection must be suitable for that cross-section
0.5 mm²Control, monitoring, signalling and measurement circuits

The 1 mm² row in Table 4.11 is therefore not, by itself, permission to install new fixed 1 mm² wiring in a home. Table 4.11 sets the maximum protective rating when another applicable rule permits that cross-section; Table 5.1 defines the field of use here.

Existing 1 mm² EMCB and EMCVB wiring

Part 8 matters for existing sections of an installation. For installations whose on-site execution began before 17 May 1986, the derogation can allow an EMCB or EMCVB 1 mm² wiring system to remain in service when it forms part of a circuit without socket outlets, subject to the conditions of that derogation. Its protective device must be adapted to the cross-section. This is an allowance for existing wiring, not a rule permitting 1 mm² in a new installation. The actual condition, date and available documentation must be established during an inspection.

Voltage drop: 3% and 5% are not AREI limits

For a preliminary check, designers often use 3% for lighting and 5% for other final circuits. These are useful design or calculation assumptions, but they are not percentages that AREI 5.2.5 sets as general hard limits. That provision refers to the rules of the trade. Present 3% and 5% explicitly as a non-binding preliminary check. A long run, a motor, an EV charging point or sensitive equipment may require a larger cross-section after the actual conditions are calculated.

Replacing an old fuse

On an existing circuit, first identify the wiring actually installed, its installation method, the expected load and any derogations that apply to its construction date. The Table 4.11 columns come afterwards. For 2.5 mm², 16 A for a fuse and 20 A for a breaker are the table ceilings; they are not instructions to increase the protective rating. For 1.5 mm², the breaker ceiling is 16 A, while a socket circuit remains subject to the applicable minimum cross-section.

Design and document

With PlanElec, you can record cross-sections, protective devices, circuits and lengths in the editor, export a PDF and run an orientational self-check. The tool helps organise data and open points. It is not a complete cable calculation, an AREI compliance certificate or a replacement for measurements or an official inspection.

Further reading